Building Insulation

A house loses heat through its walls, windows, roof and floor, and through air leaking in and out. Add insulation, change the glazing, seal the gaps and change the weather. See the temperature drop through the wall, where the heat escapes, and how much energy a year of heating would take.

How the model works

Heat flows through each layer of a wall in turn, so their thermal resistances add up. A layer of thickness d and conductivity k has R = d / k (m²K/W); the surfaces add small film resistances (0.13 inside, 0.04 outside). The U-value is the inverse of the total:

U = 1 / (R_si + Σ dᵢ/kᵢ + R_se) Q = U A ΔT

The temperature falls through each layer in proportion to its share of the resistance, so most of the drop happens across the insulation. Air leakage adds Q_vent ≈ 0.33 × n × V × ΔT watts, with n air changes per hour and V the house volume in m³.

Annual heating energy is estimated with heating degree-days (HDD): the sum over the year of how far the daily mean temperature falls below the base temperature. Energy = total heat-loss coefficient × HDD × 24 h.

The house is 10 m × 8 m with two storeys (5 m tall): 180 m² of external wall including windows, an 80 m² roof and an 80 m² ground floor (fixed U = 0.45), and 400 m³ of air. The bare wall is 13 mm plaster on 220 mm brick (k = 0.77).

Idealized steady state: no thermal bridges, solar or internal heat gains, thermal mass, moisture effects or heating-system losses. Real savings are usually smaller than this model suggests.

Guided experiments

  1. Old house. Solid brick walls, single glazing, no loft insulation, one air change per hour; 0 °C outside. Prediction: wall U ≈ 2.08 and roof U ≈ 2.56 W/m²K. The house loses about 17.3 kW, most through the walls (6.7 kW) and roof (4.3 kW).
  2. Insulate the loft with 270 mm of mineral wool. Prediction: roof U falls to 0.14, roof loss from 4.3 kW to 0.24 kW, and total loss to about 13.3 kW: the cheapest big win.
  3. Diminishing returns. Add 100 mm, then 200 mm of wall insulation. Prediction: 100 mm cuts the wall U from 2.08 to 0.34 and saves 5.6 kW. Doubling to 200 mm saves only another 0.5 kW, because U = 1/R flattens as R grows.
  4. Modern house. 150 mm PIR walls, 300 mm loft, triple glazing, 0.3 air changes per hour. Prediction: total loss about 2.7 kW, one-sixth of the old house. Air leakage and the uninsulated floor are now the largest losses.

Challenge

A wall has U = 0.30 W/m²K. You add a further 50 mm of PIR (k = 0.022). What is the new U-value, and by how much does the heat loss through 100 m² of this wall fall on a day with a 20 K temperature difference?

Reveal the explanation

R = 1/0.30 = 3.33; the PIR adds 0.05/0.022 = 2.27, so R = 5.60 and U = 0.179. The loss falls from 0.30 × 100 × 20 = 600 W to 0.179 × 100 × 20 ≈ 357 W, a saving of about 240 W.

References

  • ISO 6946:2017, Building components and building elements: thermal resistance and thermal transmittance, calculation methods.
  • CIBSE, Guide A: Environmental Design (2015), sections 3 and 4.
  • Szokolay, S. V., Introduction to Architectural Science, 3rd ed. (2014), ch. 1.